TOROIDIAL TRANSFORMERS

Toroidal Current Transformers are designed for use with ammeters, wattmeters and cross current compensation or for relay driver application. All models have an Insulation level of 600V, 10 kv BIL Full Wave, 50 - 400Hz and are CSA and UL Recognized.

Model 2


View Specifications

Model 2 Instrument Transformers, Model 2RL, Model 2RL 500, Model 2RL 600, Model 2RL 750, Model 2RL 800, Model 2RL 101, Model 2RL 121, Model 2RL 1250, Model 2RL 151, Model 2RL 201, Model 2RL 251, Model 2RL 301, Model 2RL 401, Model 2SHT, Model 2SHT 500, Model 2SHT 600, Model 2SHT 750, Model 2SHT 800, Model 2SHT 101, Model 2SHT 121, Model 2SHT 1250, Model 2SHT 151, Model 2SHT 201, Model 2SHT 251, Model 2SHT 301, Model 2SHT 401, Model 2SHL, Model 2SHL 500, Model 2SHL 600, Model 2SHL 750, Model 2SHL 800, Model 2SHL 101, Model 2SHL 121, Model 2SHL 1250, Model 2SHL 151, Model 2SHL 201, Model 2SHL 251, Model 2SHL 301, Model 2SHL 401, Model 2SFT, Model 2SFT 500, Model 2SFT 600, Model 2SFT 750, Model 2SFT 800, Model 2SFT 101, Model 2SFT 121, Model 2SFT 1250, Model 2SFT 151, Model 2SFT 201, Model 2SFT 251, Model 2SFT 301, Model 2SFT 401, Model 2SFL, Model 2SFL 500, Model 2SFL 600, Model 2SFL 750, Model 2SFL 800, Model 2SFL 101, Model 2SFL 121, Model 2SFL 1250, Model 2SFL 151, Model 2SFL 201, Model 2SFL 251, Model 2SFL 301, Model 2SFL 401, Model 2DRL, Model 2DRL 500, Model 2DRL 600, Model 2DRL 750, Model 2DRL 800, Model 2DRL 101, Model 2DRL 121, Model 2DRL 1250, Model 2DRL 151, Model 2DRL 201, Model 2DRL 251, Model 2DRL 301, Model 2DRL 401,

 

Model 2 Instrument Transformers, Model 2RL, Model 2RL-500, Model 2RL-600, Model 2RL-750, Model 2RL-800, Model 2RL -101, Model 2RL-121, Model 2RL-1250, Model 2RL-151, Model 2RL-201, Model 2RL-251, Model 2RL-301, Model 2RL-401, Model 2SHT, Model 2SHT-500, Model 2SHT-600, Model 2SHT-750, Model 2SHT-800, Model 2SHT-101, Model 2SHT-121, Model 2SHT 1250, Model 2SHT 151, Model 2SHT 201, Model 2SHT 251, Model 2SHT 301, Model 2SHT 401, Model 2SHL, Model 2SHL-500, Model 2SHL-600, Model 2SHL-750, Model 2SHL-800, Model 2SHL-101, Model 2SHL-121, Model 2SHL-1250, Model 2SHL-151, Model 2SHL-201, Model 2SHL-251, Model 2SHL-301, Model 2SHL-401, Model 2SFT, Model 2SFT-500, Model 2SFT-600, Model 2SFT-750, Model 2SFT-800, Model 2SFT-101, Model 2SFT-121, Model 2SFT-1250, Model 2SFT-151, Model 2SFT-201, Model 2SFT-251, Model 2SFT-301, Model 2SFT-401, Model 2SFL, Model 2SFL-500, Model 2SFL-600, Model 2SFL- 750, Model 2SFL-800, Model 2SFL-101, Model 2SFL-121, Model 2SFL-1250, Model 2SFL-151, Model 2SFL-201, Model 2SFL-251, Model 2SFL-301, Model 2SFL-401, Model 2DRL, Model 2DRL-500, Model 2DRL-600, Model 2DRL-750, Model 2DRL-800, Model 2DRL-101, Model 2DRL-121, Model 2DRL-1250, Model 2DRL-151, Model 2DRL-201, Model 2DRL-251, Model 2DRL-301, Model 2DRL-401,

Model 5


View Specifications

Model 5 Instrument Transformers, Model 5RL, Model 5RL 500, Model 5RL 600, Model 5RL 750, Model 5RL 800, Model 5RL 101, Model 5RL 121, Model 5RL 1250, Model 5RL 151, Model 5RL 201, Model 5RL 251, Model 5RL 301, Model 5RL 401, Model 5RL 501. Model 5RL 601, Model 5RL 750, Model 5RL 801, Model 5RL 102, Model 5RL 122, Model 5SFT, Model 5SFT 500, Model 5SFT 600, Model 5SFT 750, Model 5SFT 800, Model 5SFT 101, Model 5SFT 121, Model 5SFT 1250, Model 5SFT 151, Model 5SFT 201, Model 5SFT 251, Model 5SFT 301, Model 5SFT 401, Model 5SFT 501. Model 5SFT 601, Model 5SFT 750, Model 5SFT 801, Model 5SFT 102, Model 5SFT 122,Model 5SFL, Model 5SFL 500, Model 5SFL 600, Model 5SFL 750, Model 5SFL 800, Model 5SFL 101, Model 5SFL 121, Model 5SFL 1250, Model 5SFL 151, Model 5SFL 201, Model 5SFL 251, Model 5SFL 301, Model 5SFL 401, Model 5SFL 501. Model 5SFL 601, Model 5SFL 750, Model 5SFL 801, Model 5SFL 102, Model 5SFL 122, Model 5SHT, Model 5SHT 500, Model 5SHT 600, Model 5SHT 750, Model 5SHT 800, Model 5SHT 101, Model 5SHT 121, Model 5SHT 1250, Model 5SHT 151, Model 5SHT 201, Model 5SHT 251, Model 5SHT 301, Model 5SHT 401, Model 5SHT 501. Model 5SHT 601, Model 5SHT 750, Model 5SHT 801, Model 5SHT 102, Model 5SHT 122, Model 5SHL, Model 5SHL 500, Model 5SHL 600, Model 5SHL 750, Model 5SHL 800, Model 5SHL 101, Model 5SHL 121, Model 5SHL 1250, Model 5SHL151, Model 5SHL 201, Model 5SHL 251, Model 5SHL 301, Model 5SHL 401, Model 5SHL 501. Model 5SHL 601, Model 5SHL 750, Model 5SHL 801, Model 5SHL 102, Model 5SHL 122,

Model 5 Instrument Transformers, Model 5RL, Model 5RL-500, Model 5RL-600, Model 5RL-750, Model 5RL-800, Model 5RL-101, Model 5RL-121, Model 5RL-1250, Model 5RL-151, Model 5RL-201, Model 5RL-251, Model 5RL-301, Model 5RL-401, Model 5RL-501. Model 5RL-601, Model 5RL-750, Model 5RL-801, Model 5RL-102, Model 5RL-122, Model 5SFT, Model 5SFT-500, Model 5SFT-600, Model 5SFT-750, Model 5SFT-800, Model 5SFT-101, Model 5SFT-121, Model 5SFT-1250, Model 5SFT-151, Model 5SFT-201, Model 5SFT-251, Model 5SFT-301, Model 5SFT-401, Model 5SFT-501. Model 5SFT-601, Model 5SFT-750, Model 5SFT-801, Model 5SFT-102, Model 5SFT-122,Model 5SFL, Model 5SFL-500, Model 5SFL-600, Model5SFL-750, Model-5SFL 800, Model 5SFL-101, Model 5SFL-121, Model 5SFL-1250, Model 5SFL-151, Model 5SFL-201, Model 5SFL-251, Model 5SFL-301, Model 5SFL-401, Model 5SFL-501. Model 5SFL-601, Model 5SFL-750, Model 5SFL-801, Model 5SFL-102, Model 5SFL-122, Model 5SHT, Model 5SHT-500, Model 5SHT-600, Model 5SHT-750, Model 5SHT-800, Model 5SHT-101, Model 5SHT-121, Model 5SHT-1250, Model 5SHT-151, Model 5SHT-201, Model 5SHT-251, Model 5SHT-301, Model 5SHT-401, Model 5SHT-501. Model 5SHT-601, Model 5SHT-750, Model 5SHT-801, Model 5SHT-102, Model 5SHT-122, Model 5SHL, Model 5SHL-500, Model 5SHL-600, Model 5SHL-750, Model 5SHL-800, Model 5SHL-101, Model 5SHL-121, Model 5SHL-1250, Model 5SHL-151, Model 5SHL-201, Model 5SHL-251, Model 5SHL-301, Model 5SHL-401, Model 5SHL-501. Model 5SHL-601, Model 5SHL-750, Model 5SHL-801, Model 5SHL-102, Model 5SHL-122,

Model 6


View Specifications

Model 6 Instrument Transformers, Model 6RL, Model 6RL-101, Model 6RL-121, Model 6RL-151, Model 6RL-201, Model 6RL- 251, Model 6RL-301, Model 6RL-401, Model 6RL-501. Model 6RL-601, Model 6RL-750, Model 6RL-801, Model 6RL-102, Model 6RL-122, Model 6RL-152, Model 6SFT, Model 6SFT-101, Model 6SFT-121, Model 6SFT-151, Model 6SFT-201, Model 6SFT- 251, Model 6SFT-301, Model 6SFT-401, Model 6SFT-501. Model 6SFT-601, Model 6SFT-750, Model 6SFT-801, Model 6SFT-102, Model 6SFT-122, Model 6SFT-152, Model 6SHT, Model 6SHT-101, Model 6SHT-121, Model 6SHT-151, Model 6SHT-201, Model 6SHT-251, Model 6SHT-301, Model 6SHT-401, Model 6SHT-501. Model 6SHT-601, Model 6SHT-750, Model 6SHT-801, Model 6SHT-102, Model 6SHT-122, Model 6SHT-152, Model 6SFL, Model 6SFL-101, Model 6SFL-121, Model 6SFL-151, Model 6SFL-201, Model 6SFL-251, Model 6SFL-301, Model 6SFL-401, Model 6SFL-501. Model 6SFL-601, Model 6SFL-750, Model 6SFL-801, Model 6SFL-102, Model 6SFL-122, Model 6SFL-152, Model 6SHL, Model 6SHL-101, Model 6SHL-121, Model 6SHL-151, Model 6SHL-201, Model 6SFL-251, Model 6SHL-301, Model 6SHL-401, Model 6SHL-501. Model 6SHL-601, Model 6SHL-750, Model 6SHL-801, Model 6SHL-102, Model 6SHL-122, Model 6SHL-152, Model 6RL, Model 6RL 101, Model 6RL 121, Model 6RL 151, Model 6RL 201, Model 6RL 251, Model 6RL 301, Model 6RL 401, Model 6RL 501. Model 6RL 601, Model 6RL 750, Model 6RL 801, Model 6RL 102, Model 6RL 122, Model 6RL 152, Model 6SFT, Model 6SFT 101, Model 6SFT 121, Model 6SFT 151, Model 6SFT 201, Model 6SFT 251, Model 6SFT 301, Model 6SFT 401, Model 6SFT 501. Model 6SFT 601, Model 6SFT 750, Model 6SFT 801, Model 6SFT 102, Model 6SFT 122, Model 6SFT 152, Model 6SHT, Model 6SHT 101, Model 6SHT 121, Model 6SHT 151, Model 6SHT 201, Model 6SHT 251, Model 6SHT 301, Model 6SHT 401, Model 6SHT 501. Model 6SHT 601, Model 6SHT 750, Model 6SHT 801, Model 6SHT 102, Model 6SHT 122, Model 6SHT 152, Model 6SFL, Model 6SFL 101, Model 6SFL 121, Model 6SFL 151, Model 6SFL 201, Model 6SFL-251, Model 6SFL 301, Model 6SFL 401, Model 6SFL 501. Model 6SFL 601, Model 6SFL 750, Model 6SFL 801, Model 6SFL 102, Model 6SFL 122, Model 6SFL 152, Model 6SHL, Model 6SHL 101, Model 6SHL 121, Model 6SHL 151, Model 6SHL 201, Model 6SFL-251, Model 6SHL 301, Model 6SHL 401, Model 6SHL 501, Model 6SHL 601, Model 6SHL 750, Model 6SHL 801, Model 6SHL 102, Model 6SHL 122, Model 6SHL 152,

Model 7


View Specifications

Model 7 Instrument Transformers, Model 7RL, Model 7RL-101, Model 7RL-121, Model 7RL-151, Model 7RL-201, Model 7RL- 251, Model 7RL-301, Model 7RL-401, Model 7RL-501. Model 7RL-601, Model 7RL-750, Model 7RL-801, Model 7RL-102, Model 7RL-122, Model 7RL-152, Model 7RL-162 Model 7SFT, Model 7SFT-101, Model 7SFT-121, Model 7SFT-151, Model 7SFT-201, Model 7SFT- 251, Model 7SFT-301, Model 7SFT-401, Model 7SFT-501. Model 7SFT-601, Model 7SFT-750, Model 7SFT-801, Model 7SFT-102, Model 7SFT-122, Model 7SFT-152, Model 7SFT-162, Model 7SHT, Model 7SHT-101, Model 7SHT-121, Model 7SHT-151, Model 7SHT-201, Model 7SHT-251, Model 7SHT-301, Model 7SHT-401, Model 7SHT-501. Model 7SHT-601, Model 7SHT-750, Model 7SHT-801, Model 7SHT-102, Model 7SHT-122, Model 7SHT-152, Model 7SHT-162,  Model 7SFL, Model 7SFL-101, Model 7SFL-121, Model 7SFL-151, Model 7SFL-201, Model 7SFL-251, Model 7SFL-301, Model 7SFL-401, Model 7SFL-501. Model 7SFL-601, Model 7SFL-750, Model 7SFL-801, Model 7SFL-102, Model 7SFL-122, Model 7SFL-152, Model 7SFL-162,  Model 7SHL, Model 7SHL-101, Model 7SHL-121, Model 7SHL-151, Model 7SHL-201, Model 7SFL-251, Model 7SHL-301, Model 7SHL-401, Model 7SHL-501. Model 7SHL-601, Model 7SHL-750, Model 7SHL-801, Model 7SHL-102, Model 7SHL-122, Model 7SHL-152, Model 7SHL-162, Model 7RL, Model 7RL 101, Model 7RL 121, Model 7RL 151, Model 7RL 201, Model 7RL 251, Model 7RL 301, Model 7RL 401, Model 7RL 501. Model 7RL 601, Model 7RL 750, Model 7RL 801, Model 7RL 102, Model 7RL 122, Model 7RL 152, Model 7RL 162,  Model 7SFT, Model 7SFT 101, Model 7SFT 121, Model 7SFT 151, Model 7SFT 201, Model 7SFT 251, Model 7SFT 301, Model 7SFT 401, Model 7SFT 501. Model 7SFT 601, Model 7SFT 750, Model 7SFT 801, Model 7SFT 102, Model 7SFT 122, Model 7SFT 152, Model 7SFT 162, Model 7SHT, Model 7SHT 101, Model 7SHT 121, Model 7SHT 151, Model 7SHT 201, Model 7SHT 251, Model 7SHT 301, Model 7SHT 401, Model 7SHT 501. Model 7SHT 601, Model 7SHT 750, Model 7SHT 801, Model 7SHT 102, Model 7SHT 122, Model 7SHT 152, Model 7SHT 162,  Model 7SFL, Model 7SFL 101, Model 7SFL 121, Model 7SFL 151, Model 7SFL 201, Model 7SFL-251, Model 7SFL 301, Model 7SFL 401, Model 7SFL 501. Model 7SFL 601, Model 7SFL 750, Model 7SFL 801, Model 7SFL 102, Model 7SFL 122, Model 7SFL 152, Model 7SFL 162, Model 7SHL, Model 7SHL 101, Model 7SHL 121, Model 7SHL 151, Model 7SHL 201, Model 7SFL-251, Model 7SHL 301, Model 7SHL 401, Model 7SHL 501, Model 7SHL 601, Model 7SHL 750, Model 7SHL 801, Model 7SHL 102, Model 7SHL 122, Model 7SHL 152, Model 7SHL 162,

Model 8

View Specifications        

Model 19
Moodel 56
Model 76
Model 112
Model 113
Model 114
Model 115
Model 117
Model 170
 

Electromagnetic Industries LLP

1507 Beaumont Street  Baytown, TX 77521 FAX: 281-422-5275 PHONE: 281-422-5225

 

BGFL 159, BGFL 259, BGFL 137, BGFL 147, BGFL 157, BGFL 139, BGFL 149, BGFL 237, BGFL, 247, BGFL 257, BGFL 239, BGFL 249

 

The BGFL Class 1 Ground Fault Relay Manufactured by Electromagnetic Industries LLP meets NEC service entrance equipment standards. The BGFL Operates with molded case power circuit breakers,  bolted pressure switches, or fusible disconnect switches.

The BGFL, has an Electro-mechanical relay output positive “ON” and “OFF”. The BGFL has two styles, “Standard” (without interlock) and “Zone Interlocking”, Integral test panel with “Push to Test” and “Shunt Trip Bypass” pushbuttons for proper testing of device with the ability to trip or not trip the protective device. It also has a visual trip indicator, adjustable time delay, discrete current threshold adjustment.

 

 

The BGFL Ground Fault Relay Manufactured by Electromagnetic Industries LLP along with the accompanied sensor are used together to provide a system for detecting ground fault current in a grounded AC power System. When the system detects a fault, of a preselected level for the duration of a preselected time delay, the relay initiates a trip of the Shunt Trip Device to open the contacts/breaker and clear the Ground Fault.

 

The Electromagnetic Industries BGFL Ground Fault Relay has current trip set points of 5 – 60Amps, 30 – 370 Amps and 100 to 1200 Amps. The BGFL is UL Listed.

 

GFL 041X , GFL 051X , GFL 058X, GFL 080X ,GFL 101X ,

 

The GFL Ground Fault Sensor manufactured by Electromagnetic Industries LLP is used with the BGFL and GFP Ground Fault Relays to provide a way to detect and protect from Ground Fault Conditions in Grounded AC power systems.

 

GFP 111, GFP 112, GFP 113, GFP 121, GFP 122, GFP 123, GFP 131, GFP 132, GFP 133, GFP 141, GFP 142, GFP 143, GFP 211, GFP 212, GFP 213, GFP 222, GFP 223, GFP 231, GFP 232, GFP 233, GFP 241, GFP 242, GFP 243

 

The GFP Ground Fault Relay Manufactured by Electromagnetic Industries LLP is a Class 1 relay that  meets NEC service entrance equipment standards. The GFP Operates with molded case power circuit breakers,  bolted pressure switches, or fusible disconnect switches.

The GFP, has an Electro-mechanical relay output positive “ON” and “OFF” and  has two styles, “Standard” (without interlock) and “Zone Interlocking”, Integral test panel with “Push to Test” and “Shunt Trip Bypass” pushbuttons for proper testing of device with the ability to trip or not trip the protective device. It also has a visual trip indicator, real time Ground Fault level display, adjustable time delay, discrete current threshold adjustment. The GFP also retains the information of what the Ground Fault level was at trip/power down.

 

The GFP Ground Fault Relay Manufactured by Electromagnetic Industries LLP along with the accompanied sensors are used to provide a system for detecting ground fault current in a grounded AC power System. When the system detects a fault it will display the level and at a preselected level for the duration of a preselected time delay, the relay initiates a trip of the Shunt Trip Device to open the contacts/breaker and clear the Ground Fault.

 

The Electromagnetic Industries BGFL Ground Fault Relay has current trip set points of 5 – 60Amps, 30 – 370 Amps and 100 to 1200 Amps. The BGFL is UL Listed.

 

 

GFM 252, GFM 262, GFM 353, GFM 363, GFM 425, GFM 453, GFM 363B, GFM 375D

 

The GFM manufactured be Electromagnetic Industries is a (Class 1) Ground Fault protection system used to minimize damage to equipment due to arcing ground faults. The GFM system is designed for all poly-phase applications and is ideal for motor control, motor control centers and high voltage starters

 

The GFM relay comes in 3 Model/Series. GFM 200, GFM 300 and GFM 400.

 

CTD 1, CTD 2, CTD 3, CTD 4, CTD 5, CTD 4-120, CTD 4-240, CTD 5-120, CTD 5-240

 

The CTD-1 manufactured by Electromagnetic Industries is designed to provide a source of energy for a circuit breaker or switch to trip during a loss of normal AC or DC power.

These devices are protected against inadvertent short circuits, input from line surges and inductive kickback from trip coils. The nominal 120Volts AC or 125 DC is applied between “AC” and ‘COM” terminals. This voltage is half wave rectified and applied across the trip capacitor to give the output trip voltage. The charge stored in the capacitor (330 uF @168 VDC) is available between “ ” and “COM” terminals for the trip coil operation. The half wave rectification

circuitry provides the advantage of maintaining a common neutral connection from the input and output while still maintaining the charge in the trip capacitor after a loss of control power.

The capacitor is continuously charged when control power is applied. This provides energy for normal trip coil operation. Because mechanical relays are not used, energy from the trip coil operation is immediately available with the loss of control power. When the control power returns, the capacitor  will recharge and will be able to supply energy for the next trip coil operation.

 

The CTD-2 manufactured by Electromagnetic Industries is designed to provide a source of energy for a circuit breaker or switch to trip during a loss of normal AC or DC power.

These devices are protected against inadvertent short circuits, input from line surges and inductive kickback from trip coils. The nominal 120Volts AC or 125 DC is applied between “AC” and ‘COM” terminals. This voltage is half wave rectified and applied across the trip capacitor to give the output trip voltage. The charge stored in the capacitor (1500 uF @ 168 VDC) is available between “ ” and “COM” terminals for the trip coil operation. The half wave rectification

circuitry provides the advantage of maintaining a common neutral connection from the input and output while still maintaining the charge in the trip capacitor after a loss of control power.

The capacitor is continuously charged when control power is applied. This provides energy for normal trip coil operation. Because mechanical relays are not used, energy from the trip coil operation is immediately available with the loss of control power. When the control power returns, the capacitor  will recharge and will be able to supply energy for the next trip coil operation.

 

 

The CTD-3 manufactured by Electromagnetic Industries is designed to provide a source of energy for a circuit breaker or switch to trip during a loss of normal AC or DC power.

These devices are protected against inadvertent short circuits, input from line surges and inductive kickback from trip coils. The nominal 240Volts AC is applied between “AC” and ‘COM” terminals. This voltage is half wave rectified and applied across the trip capacitor to give the output trip voltage. The charge stored in the capacitor (330 uF @ 338 VDC) is available between “ ” and “COM” terminals for the trip coil operation. The half wave rectification

circuitry provides the advantage of maintaining a common neutral connection from the input and output while still maintaining the charge in the trip capacitor after a loss of control power.

The capacitor is continuously charged when control power is applied. This provides energy for normal trip coil operation. Because mechanical relays are not used, energy from the trip coil operation is immediately available with the loss of control power. When the control power returns, the capacitor  will recharge and will be able to supply energy for the next trip coil operation.

 

The CTD-4-120 manufactured by Electromagnetic Industries is designed to provide a source of energy for a circuit breaker or switch to trip during a loss of normal AC or DC power.

These devices are protected against inadvertent short circuits, input from line surges and inductive kickback from trip coils. The nominal 120Volts AC is applied between “AC” and ‘COM” terminals. The charge stored in the capacitor (4500 uF @ 168 VDC) is available between “ ” and “COM” terminals for the trip coil operation. The half wave rectification

circuitry provides the advantage of maintaining a common neutral connection from the input and output while still maintaining the charge in the trip capacitor after a loss of control power.

The capacitor is continuously charged when control power is applied. This provides energy for normal trip coil operation. Because mechanical relays are not used, energy from the trip coil operation is immediately available with the loss of control power. When the control power returns, the capacitor  will recharge and will be able to supply energy for the next trip coil operation.

 

 The CTD-4-240 manufactured by Electromagnetic Industries is designed to provide a source of energy for a circuit breaker or switch to trip during a loss of normal AC or DC power.

These devices are protected against inadvertent short circuits, input from line surges and inductive kickback from trip coils. The nominal 240Volts AC is applied between “AC” and ‘COM” terminals. The charge stored in the capacitor (990 uF @ 338 VDC) is available between “ ” and “COM” terminals for the trip coil operation. The half wave rectification

circuitry provides the advantage of maintaining a common neutral connection from the input and output while still maintaining the charge in the trip capacitor after a loss of control power.

The capacitor is continuously charged when control power is applied. This provides energy for normal trip coil operation. Because mechanical relays are not used, energy from the trip coil operation is immediately available with the loss of control power. When the control power returns, the capacitor  will recharge and will be able to supply energy for the next trip coil operation.

 

 

The CTD-5-120 manufactured by Electromagnetic Industries is designed to provide a source of energy for a circuit breaker or switch to trip during a loss of normal AC or DC power. The CTD-5 also has an alarm relay to continuously monitor the input and output of the device.  This relay is energized when the proper input and output voltages are present. The relay changes state if the input voltage is lost, or the output voltage drops to 85%. An LED indicates normal operation.

These devices are protected against inadvertent short circuits, input from line surges and inductive kickback from trip coils. The nominal 120Volts AC is applied between “AC” and ‘COM” terminals. The charge stored in the capacitor (4500 uF @ 168 VDC) is available between “ ” and “COM” terminals for the trip coil operation. The half wave rectification

circuitry provides the advantage of maintaining a common neutral connection from the input and output while still maintaining the charge in the trip capacitor after a loss of control power.

The capacitor is continuously charged when control power is applied. This provides energy for normal trip coil operation. Because mechanical relays are not used, energy from the trip coil operation is immediately available with the loss of control power. When the control power returns, the capacitor  will recharge and will be able to supply energy for the next trip coil operation.

 

 The CTD-5-240 manufactured by Electromagnetic Industries is designed to provide a source of energy for a circuit breaker or switch to trip during a loss of normal AC or DC power. The CTD-5 also has an alarm relay to continuously monitor the input and output of the device.  This relay is energized when the proper input and output voltages are present. The relay changes state if the input voltage is lost, or the output voltage drops to 85%. An LED indicates normal operation.

These devices are protected against inadvertent short circuits, input from line surges and inductive kickback from trip coils. The nominal 240Volts AC is applied between “AC” and ‘COM” terminals. The charge stored in the capacitor (990 uF @ 338 VDC) is available between “ ” and “COM” terminals for the trip coil operation. The half wave rectification

circuitry provides the advantage of maintaining a common neutral connection from the input and output while still maintaining the charge in the trip capacitor after a loss of control power.

The capacitor is continuously charged when control power is applied. This provides energy for normal trip coil operation. Because mechanical relays are not used, energy from the trip coil operation is immediately available with the loss of control power. When the control power returns, the capacitor  will recharge and will be able to supply energy for the next trip coil operation.

 

SPVR, SPVR-120, SPVR-208, SPVR-240, SPVR-308, SPVR-415, SPVR-480, SPVR-575

 

The SPVR (Three Phase Voltage Monitor) manufactured by Electromagnetic Industries is designed to protect electrical equipment from Phase Loss, Phase Unbalance, Phase Reversal, Under voltage and Overvoltage conditions.

 

A correctly installed SPVR (Three Phase Voltage Monitor) Voltage Sensing Relay will protect from Phase Loss, Phase Unbalance, Phase Reversal, Under voltage and Overvoltage conditions. The SPVR has an adjustable time delay for the trip as well as for the reset. It also has an adjustment for the Phase Unbalance (from 2% to 8%). The Phase Reversal is an instantaneous trip regardless of what the time delay is set for. The SPVR will hold in memory the condition that tripped the unit even after a power loss. The trip can be identified by pressing the “FAULT INDICATION” pushbutton up to 7 days after the fault. The SPVR will automatically reset at power up.

 

OCP

 

1-OCP, 1-OCP-100, 1-OCP-200, 1-OCP-400, 3-OCP, 3-OCP-100, 3-OCP-200, 3-OCP-400

 

A Current Transformer secondary should never be open circuited while the Current Transformer primary circuit is energized. If this situation should occur there is a possibility of developing extremely high voltages which could be dangerous to personnel or cause an insulation breakdown.

The 1-OCP series of Open Circuit Protectors manufactured by Electromagnetic Industries LLP. are voltage sensing devices using high speed shorting SCR switches. When the secondary peak voltage exceeds the clamping voltage value, the SCR operates, shorting the C.T. secondary

and reducing the voltage to about 2 volts in less than 1/4 cycle. This process repeats each current polarity reversal. The protection is activated each half cycle.

 The single  element Open Circuit Protector is provided with two terminals for connection across the secondary of  the C.T’s and in parallel with the burden. It can also be connected across the current terminals of a protective relay, meter or other current operated device without affecting the operation of the device. Secondary polarity of the C.T.’s is not critical to the OCP.

The OCP also provides protection against high secondary voltage transients, which may damage the burden or secondary winding. If the transient voltage exceeds the voltage clamping limit, the Open Circuit Protector will trigger. After triggering, the voltage will fall to about 2 volts and remain there until the next zero crossing of the current waveform at which time the device resets and the cycle repeats as necessary. In the transient mode of protection, triggering will

occur only on the half cycle where the transient appears. The leakage current of the OCP is insignificant and will not cause a ratio or phase angle error in the Current Transformer accuracy.

Metering class C.T.’s with a rating factor of 2 could operate up to 10 amps on a continuous basis. The OCP is designed to tolerate both this  condition and (80 amp RMS) for 2 seconds. 1-OCP

 

A Current Transformer secondary should never be open circuited while the Current Transformer primary circuit is energized. If this situation should occur there is a possibility of developing extremely high voltages which could be dangerous to personnel or cause an insulation breakdown.

The 3-OCP series of Open Circuit Protectors manufactured by Electromagnetic Industries LLP. are voltage sensing devices using high speed shorting SCR switches. When the secondary peak voltage exceeds the clamping voltage value, the SCR operates, shorting the C.T. secondary

and reducing the voltage to about 2 volts in less than 1/4 cycle. This process repeats each current polarity reversal. The protection is activated each half cycle.

 The three  element Open Circuit Protector is provided with two terminals (for each phase or circuit) for connection across the secondary of  the C.T’s and in parallel with the burden. It can also be connected across the current terminals of a protective relay, meter or other current operated device without affecting the operation of the device. Secondary polarity of the C.T.’s is not critical to the OCP.

The OCP also provides protection against high secondary voltage transients, which may damage the burden or secondary winding. If the transient voltage exceeds the voltage clamping limit, the Open Circuit Protector will trigger. After triggering, the voltage will fall to about 2 volts and remain there until the next zero crossing of the current waveform at which time the device resets and the cycle repeats as necessary. In the transient mode of protection, triggering will

occur only on the half cycle where the transient appears. The leakage current of the OCP is insignificant and will not cause a ratio or phase angle error in the Current Transformer accuracy.

Metering class C.T.’s with a rating factor of 2 could operate up to 10 amps on a continuous basis. The OCP is designed to tolerate both this  condition and (80 amp RMS) for 2 seconds.

 

 

The OCP (Open Circuit Protector) manufactured by Electromagnetic Industries comes in two configurations, single and three phase and three voltage levels, 100, 200 and 400 VAC.

 

Model 2 CT

Model 2DT

Model 5 CT

Model 5 DRL

Model 6 CT

Model 7 CT

Model 8 CT

Model 19 CT

 