POTENTIAL TRANSFORMERS (MODEL 467)

(120 VOLT)

Potential Transformers are encased in a thermoplastic case with the core and windings encapsulated in resin. They are designed for line to line operation but may also be used in a line to neutral or line to ground configuration at 58% of rated voltage. All transformers with rated voltages 346 Volts and below are ANSI C57.13 Group 1. All transformers rated for 480 and 600 Volt are Group 2.

DOWNLOAD MODEL 467 (120 VOLT) SCHEMATIC

Description

Model 467 (120 VOLT)

Frequency: 60 Hz
Standard Secondary Voltage: 120 VAC
Insulation Level: 600 Volts, 10Kv BIL Full Wave
Accuracy Class: +/- 1% at all burdens up to 5VA at 1.0 and 0.95 P.F.
Thermal Rating: 40 VA @ 30C amb and 27 VA @ 55C amb


Terminals are No. 6-32 binding head screws and cup washer.

Recommend using a 0.40 Amp fuse in the secondary to protect the transformer.

All transformers listed with the exception of the 480v and 600v are ANSIC57.13 Group 1. The 480v and 600v are Group 2.