CAPACITOR TRIP DEVICE (CTD-4)

The Model CTD (Capacitor Trip Devices) manufactured by Electromagnetic Industries are designed to provide a source of energy for a circuit breaker or switch to trip during a loss of normal AC or DC power.

DOWNLOAD CTD-4 (120 & 240 VOLT) SCHEMATIC

Description

CTD-4 (120 VOLT)

Normal Input Voltage: 240 Vac
Max. Input Voltage: 280 Vac
Frequency: 0-400 Hz
Available Energy: 19 joules, +/- 20% @25 Deg C
Normal Output Voltage: 338 VDC
Normal Charge Time: Approximate charge time to 90% at 60Hz/25C (350mS)
Capacitance: 330uF, +/- 20% @25 Deg C
Temp. influence on Capacitor: (-10% at -30 Deg C, +5% at 60 Deg C)
Operating Temperature: -30 Deg C to 60 Deg C
Storage Temp Range: -50 Deg C to 80 Deg C
Short Circuit Protection: Continuous
Mounting: Vertical or Horizontal
Input Surge Protection: Mov Protection to 65 joules single pulse surge

 

CTD-4 (240 VOLT)

Normal Input Voltage: 240 Vac
Max. Input Voltage: 280 Vac
Frequency: DC to 400 Hz
Available Energy: 57 joules
Normal Output Voltage: 338 VDC
Approx. Charge Time: 570mS to 90% at 25C
Capacitance: 990uF, +/- 20% @25 Deg C
Temp. influence on Capacitor: (-10% at -30 Deg C, +5% at 60 Deg C)
Operating Temperature: -30 Deg C to 60 Deg C
Storage Temp Range: -50 Deg C to 80 Deg C
Short Circuit Protection: Continuous
Mounting: Vertical or Horizontal
Input Surge Protection: Mov Protection to 65 joules single pulse surge