CAPACITOR TRIP DEVICE (CTD-1)

(120V 330UF)

The Model CTD (Capacitor Trip Devices) manufactured by Electromagnetic Industries are designed to provide a source of energy for a circuit breaker or switch to trip during a loss of normal AC or DC power.

DOWNLOAD CTD-1 (120V 330UF) SCHEMATIC

Description

CTD-1 (120V 330UF)

Normal Input Voltage: 120 Vac, 125 Volts DC
Max. Input Voltage: 140 Vac, 125 Vdc (Surge Protected)
Frequency: 0-400 Hz
Available Energy: 4.72 joules, +/- 20% @25 Deg C
Normal Output Voltage: 170Vdc (w/ 120 Vac Input) and 125Vdc (w/ 125 Vdc Input)
Normal Charge Time: 170mSec
Capacitance: 330uF, +/- 20% @25 Deg C
Operating Temperature: -30 Deg C to 60 Deg C
Storage Temp Range: -50 Deg C to 80 Deg C
Short Circuit Protection: Continuous
Mounting: Vertical or Horizontal
Input Surge Protection: Mov Protection to 65 joules single Pulse surge