Description
Model 460 (120 VOLT)
Frequency: 50/60 Hz
Standard Secondary Voltage: 120 VAC
Insulation Level: 600 Volts, 10Kv BIL Full Wave
Accuracy Class: 0.6W, 1.2 X @60Hz and 0.5 @ 10VA, 1.0 @ 20VA at 50Hz
Thermal Rating: 50Hz 125 VA @ 30C amb and 60Hz 150 VA @ 30C amb
Terminals are No. 10-32 brass studs with flat washer, lock washer and nut.
Recommend using a 1.6 Amp fuse in the secondary to protect the transformer.
All transformers listed with the exception of the 480v and 600v are ANSIC57.13 Group 1. The 480v and 600v are Group 2.
Model 460 (240 VOLT)
Frequency: 50/60 Hz
Standard Secondary Voltage: 240 VAC
Insulation Level: 600 Volts, 10Kv BIL Full Wave
Accuracy Class: 0.6W, 1.2 X @60Hz and 0.5 @ 10VA, 1.0 @ 20VA at 50Hz
Thermal Rating: 50Hz 125 VA @ 30C amb and 60Hz 150 VA @ 30C amb
Terminals are No. 10-32 brass studs with flat washer, lock washer and nut.
Recommend using a 0.75 Amp fuse in the secondary to protect the transformer.
All transformers listed with the exception of the 480v and 600v are ANSIC57.13 Group 1. The 480v and 600v are Group 2.