Made in
the USA
Accredited
ISO 9001 Certified

← Back to Electronics

Part Numbers

Part Number
CTD-1

Capacitor Trip Device Model CTD-1

The Model CTD (Capacitor Trip Devices) manufactured by Electromagnetic Industries are designed to provide a source of energy for a circuit breaker or switch to trip during a loss of normal AC or DC power.

Normal Input Voltage120VAC, 125VDC
Max Input Voltage140VAC, 125VDC (Surge Protected)
Frequency0–400 Hz
Available Energy4.72 joules, ±20% @25°C
Normal Output Voltage170VDC (w/ 120VAC Input), 125VDC (w/ 125VDC Input)
Normal Charge Time170ms
Capacitance330µF, ±20% @25°C
Operating Temperature-30°C to 60°C
Storage Temperature-50°C to 80°C
Short Circuit ProtectionContinuous
MountingVertical or Horizontal
Input Surge ProtectionMOV Protection to 65 joules single pulse surge