Made in
the USA
Accredited
ISO 9001 Certified

← Back to Electronics

Part Numbers

Part Number
CTD-4 120V
CTD-4 240V

Capacitor Trip Device Model CTD-4

The Model CTD (Capacitor Trip Devices) manufactured by Electromagnetic Industries are designed to provide a source of energy for a circuit breaker or switch to trip during a loss of normal AC or DC power. The CTD-4 is available in 120V and 240V configurations.

CTD-4 (120 Volt)
Normal Input Voltage120VAC
Max Input Voltage140VAC
Frequency0–400 Hz
Available Energy19 joules, ±20% @25°C
Normal Output Voltage338VDC
Normal Charge Time350ms to 90% at 60Hz/25°C
Capacitance330µF, ±20% @25°C
CTD-4 (240 Volt)
Normal Input Voltage240VAC
Max Input Voltage280VAC
FrequencyDC to 400 Hz
Available Energy57 joules
Normal Output Voltage338VDC
Normal Charge Time570ms to 90% at 25°C
Capacitance990µF, ±20% @25°C
Common
Temp Influence on Capacitor-10% at -30°C, +5% at 60°C
Operating Temperature-30°C to 60°C
Storage Temperature-50°C to 80°C
Short Circuit ProtectionContinuous
MountingVertical or Horizontal
Input Surge ProtectionMOV Protection to 65 joules single pulse surge