Made in
the USA
Accredited
ISO 9001 Certified

← Back to LV CT's

Part Numbers

Part Number Ratio
100-500 50:5
100-600 60:5
100-750 75:5
100-800 80:5
100-101 100:5
100-121 120:5
100-151 150:5
100-201 200:5
100-251 250:5
100-301 300:5
100-401 400:5
100-501 500:5
100-601 600:5
100-701 700:5
100-751 750:5
100-801 800:5
100-102 1000:5
100-122 1200:5
100-132 1300:5
100-142 1400:5
100-152 1500:5
100-162 1600:5
100-202 2000:5
100-252 2500:5
100-302 3000:5
100-500-1 50:1
100-600-1 60:1
100-750-1 75:1
100-800-1 80:1
100-101-1 100:1
100-121-1 120:1
100-151-1 150:1
100-201-1 200:1
100-251-1 250:1
100-301-1 300:1
100-401-1 400:1
100-501-1 500:1
100-601-1 600:1
100-801-1 800:1
100-102-1 1000:1
100-122-1 1200:1
100-132-1 1300:1
100-142-1 1400:1
100-152-1 1500:1
100-162-1 1600:1
100-202-1 2000:1
100-252-1 2500:1

Toroidal Current Transformer Model 100 (4" dia.)

Toroidal Current Transformers designed for relay and metering applications, for use with ammeters, wattmeters, cross current compensation, or relay driver applications. All models have an insulation level of 600V, 10 kV BIL Full Wave, 50–400 Hz and are CSA and UL Recognized.

Ratio200:5 to 3000:5
Window Size4.00" Diameter
ApplicationRelay and Metering
Frequency50–400 Hz
Insulation Level600V, 10kV BIL Full Wave
StandardsCSA 66.1-06, CSA 66.2-06, IEEE C57.13, UL 506
WeightApprox. 10 lbs.
  • Terminals are brass studs No. 8-32 UNC with one flat washer, one lock washer and one nut each.
  • Mounting Bracket Kits sold separately (P/N 1121A00018).
  • Other ratios and multi-ratio configurations available on request.
  • 5 AMP secondary standard.